Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of US$ 1500/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
S/N | Item | Unit | Value | |||
1 | Rated Voltage | kV | 12 | 15 | 24 | |
2 | Rated Frequency | Hz | 50/60 | |||
3 | Rated Current | A | 630 , 1250 | |||
4 | Rated short-circuit breaking current | kA | 20 , 25 | |||
5 | Rated peak withstand current (peak) | 50 , 63 | ||||
6 | Rated short-circuit withstand current | 20 , 25 | ||||
7 | Rated short circuit duration | S | 4 | |||
8 | Rated short-circuit closing current (peak) | kA | 50 , 63 | |||
9 | Rated operating sequence | 0-0.3s-C0-180s-CO | ||||
10 | Mechanical life | Times | 10000/disconnecting switch 2000 | |||
11 | Breaking times of rated current | 5000 | ||||
12 | Breaking times of rated short-circuit breaking current | 30 | ||||
13 | Power frequency withstand voltage in 1min | Wet test/dry test | kV | 42/48 | 50/55 | 65/79 |
14 | Lightning impulse withstand voltage (peak) inter-phase, over the ground/fracture | 75/85 | 88/100 | 125/145 | ||
15 | Secondary loop l min power frequency voltage (except electronic devices) | V | 2000 |
S/N | Name | Unit | Parameter | ||
1 | Rated Voltage | kV | 12 | 15 | 24 |
2 | Clearance between open contacts | mm | 9±0.5 | 11±0.5 | 14±0.5 |
3 | Over-travel of contact | mm | 3±0.5 | 3±0.5 | 3±0.5 |
4 | Average opening speed | m/s | 1.1±0.2 | 1.2±0.2 | 1.4±0.2 |
5 | Average closing speed | m/s | 0.6±0.2 | 0.8±0.2 | 1.0±0.2 |
6 | Closing contact bounce time | ms | ≤2 | ||
7 | Resistance of each phase loop | μΩ | ≤120 with isolating switch≤200 | ||
8 | Closing time | ms | 25~60 | ||
9 | Opening time | ms | 18~45 | ||
10 | Three-phase heterogeneity | mm | ≤2 | ||
11 | Inter-phase center distance | mm | 340 | 340 | 380 |