Customization: | Available |
---|---|
Type: | Power |
Structure: | Protection |
Still deciding? Get samples of US$ 3413/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
function | describe | |
San Yao |
Maximum support for 8-loop fusion line interval | |
public |
Telemetry: Two sets of bus voltage | |
Remote signaling: power module, reset, cabinet door | ||
Remote control: Battery activation | ||
Each group of lines |
4-channel telemetry: IA, IB, IC, 310 | |
5-way remote signaling: separation, closing, non stored energy, grounding knife, backup | ||
2-channel remote control: opening and closing | ||
Sampling accuracy | Voltage and current level 0.2, power level 0.5, frequency level ± 0.01 | |
Remote signaling resolution | ≤2ms, Anti shake 1~65535ms can be set | |
remote control | On/off ≥ 105, pulse width 1~65535ms can be set | |
data transmission |
communication interface | 6 serial ports RS232/RS485 can be switched on-site, 2 RJ45 ports |
Communication protocol | IEC60870-5-101,IEC60870-5-104, Support parameter configuration and file upload extension functions | |
Communication cascade | Line loss module, dehumidification module, battery detection module, relay protection, measuring instrument | |
Support multiple master stations, receiving remote control commands from only one master station at a time | ||
Historical data storage |
Circular storage of 1024 TCOS event records, with file transfer capability for uploading | |
Circular storage of 31 days of fixed-point records, with file transfer capability for uploading. 96 fixed-point data are generated at equal intervals every day | ||
Cycle storage of extreme value records for 31 days, which can be uploaded via file transfer. One extreme value record is generated per day | ||
30 remote control operation records can be stored in a loop and uploaded via file transfer | ||
Forward and upload the daily frozen electric energy file generated by the line loss module, as well as the power reverse electric energy freezing value file | ||
Fault recording |
64 sets of waveform data are stored in a loop and can be uploaded to the main station via file transfer | |
The starting conditions for waveform recording include overcurrent fault, line voltage loss, zero sequence voltage, and sudden changes in zero sequence current, which can be set separately or in combination | ||
The recording content includes waveform data for the first 4 cycles before the occurrence of the fault and the last 8 cycles after the occurrence of the fault. The number of recording points is 128 per cycle, and the recording data includes voltage, current, and switch position; Meet the recording requirements for 12 circuits | ||
The recording file format follows the format defined in the Comtrade 1999 standard, consisting of CFG (configuration file, ASCI text) and DAT (data file, binary format) files | ||
relay protection |
Quick break, overcurrent, overload, zero sequence overcurrent, triple reclosing, current blocking, anti surge misoperation, voltage exceeding limit, current exceeding limit, PT voltage detection | |
Adaptive local feeder automation, voltage time type local feeder automation, voltage current time type local feeder automation | ||
Voltage exceeding limit, current exceeding limit, PT voltage detection | ||
information safety |
Integrated security chip, supporting the parsing function of X.509 standard format SM2 digital certificate, SM1 data encryption and decryption function, SM2 algorithm signature and authentication function, SM2 algorithm public-private key pair generation function, and message authentication code MAC calculation and verification function | |
The working status of the security chip can be monitored, and maintenance operations on the device can only be carried out through permission authentication | ||
DC voltage | 2 routes, level 0.2 | |
temperature | 1 channel, real-time response to the internal environmental conditions of the device | |
At the right time | GPS B code timing, SNTP network timing, protocol timing |