ltem | Unit | Techincal parameter | ||
Rated voltage | kV | 12 | ||
Insulating medium | solidity | |||
Rated frequency | Hz | 50/60 | ||
Rated current | A | 1250 | ||
Temperature rise test current | 1.1Ir | |||
Rated power frequency 1min withstand voltage (relative) | kV | 42 | ||
Peak rated lightning impulse withstand voltage (1.2/50ms) (relative) | kV | 75 | ||
Rated short-time withstand current and duration | kA/s | 31.5/4 | ||
Rated peak withstand current | kA | 80 | ||
Duration of ignition | s | 1 | ||
Short-time power frequency withstand voltage of auxiliary and control circuits | kV | 2 | ||
Class of protection | Cabinet housing | IP4X | ||
compartment | IP2X | |||
Local discharge | pC | Full cabinet (1.1Ur) ≤20pC | ||
A single insulation component (1.1Ur) ≤5pC |